Skip to content

Create OPCUA.md #10

New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

Open
wants to merge 4 commits into
base: master
Choose a base branch
from
Open

Create OPCUA.md #10

wants to merge 4 commits into from

Conversation

esmith1729
Copy link
Contributor

Add file for general OPCUA knowledge

@esmith1729 esmith1729 changed the title Create OPCUA.cmd Create OPCUA.md May 8, 2025
Copy link
Contributor

@Tom-Willemsen Tom-Willemsen left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Thanks, this is looking close.

A few comments to improve readability below

More info can be found [here on Wikipedia for a general overview](https://en.wikipedia.org/wiki/OPC_Unified_Architecture), or for a more detailed description from [OPC Foundation](https://opcfoundation.org/about/what-is-opc/).

## How is authentication handled?
Currently, the IOC does not seem to be able to support encrypted message security policy. It does, however, support “None” security mode, and connecting with a username and password, which also appears to require sending the password encrypted with Basic256 (username and password connection works with None security mode, but does not work if there is no certificate and private key provided via the `opcuaCLientCertificate` option in the `st-common.cmd` or `st.cmd` file, which loads the IOC with some other options.
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Suggested change
Currently, the IOC does not seem to be able to support encrypted message security policy. It does, however, support None security mode, and connecting with a username and password, which also appears to require sending the password encrypted with Basic256 (username and password connection works with None security mode, but does not work if there is no certificate and private key provided via the `opcuaCLientCertificate` option in the `st-common.cmd` or `st.cmd` file, which loads the IOC with some other options.
Currently, the IOC does not seem to be able to support encrypted message security policy. It does, however, support "None" security mode, and connecting with a username and password, which also appears to require sending the password encrypted with Basic256 (username and password connection works with None security mode, but does not work if there is no certificate and private key provided via the `opcuaCLientCertificate` option in the `st-common.cmd` or `st.cmd` file, which loads the IOC with some other options.

Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

which loads the IOC with some other options.

It's unclear to me exactly what this means or refers to?


More info can be found [here on Wikipedia for a general overview](https://en.wikipedia.org/wiki/OPC_Unified_Architecture), or for a more detailed description from [OPC Foundation](https://opcfoundation.org/about/what-is-opc/).

## How is authentication handled?
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

I get that you probably copied these headers from a message/comment I sent previously - but I think they might be clearer on the wiki as headings like "Authentication", "Communication", "Troubleshooting" etc.

I've put this comment once but applies to most of the headers in this file

Currently, authentication configurations in Windows only seem to work with username and password. This is likely due to functionality missing from the `open62541` library, the open source library that we use in conjunction with `opcua` EPICS module. A username and password is set on the PLC itself, and those values can be read at IOC startup to authenticate, and sent via Basic256 encryption to the PLC to sign in. When implementing/installing onto a new instrument, the `client_private_key.pem`, `cert.txt` (which will need to be edited to reflect current username and password for the target PLC/server), and `OPCUA_01.cmd` should be moved from the Experiment Controls non-public share `OPCUA` folder, to the instrument's configurations area, in a new folder that should be named `opcua`. If done properly, the `opcua` EPICS module should be able to pick up the user name and password, log in to the OPC server properly, and begin a connection.

## Do any settings in the PLC side need to be adjusted to get communicating properly?
On occasion, a client certificate needs to be trusted manually, from the PLC technician side. However, things *_should_* be set up on our PLCs currently deployed; this step is done in deployment/implementation. A security policy might be set that is not what the IOC is trying to use, if everything else seems fine but you are unable to connect. Lastly, another person might be connected to the server (perhaps testing an IOC or something), and they would need to be kicked off in order for the IOC to communicate properly. Speak with Tim Carter or a member of his team to see if this is the case.
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

or a member of his team to see if this is the case.

Which team is this?

## How is authentication handled?
Currently, the IOC does not seem to be able to support encrypted message security policy. It does, however, support “None” security mode, and connecting with a username and password, which also appears to require sending the password encrypted with Basic256 (username and password connection works with None security mode, but does not work if there is no certificate and private key provided via the `opcuaCLientCertificate` option in the `st-common.cmd` or `st.cmd` file, which loads the IOC with some other options.

Currently, authentication configurations in Windows only seem to work with username and password. This is likely due to functionality missing from the `open62541` library, the open source library that we use in conjunction with `opcua` EPICS module. A username and password is set on the PLC itself, and those values can be read at IOC startup to authenticate, and sent via Basic256 encryption to the PLC to sign in. When implementing/installing onto a new instrument, the `client_private_key.pem`, `cert.txt` (which will need to be edited to reflect current username and password for the target PLC/server), and `OPCUA_01.cmd` should be moved from the Experiment Controls non-public share `OPCUA` folder, to the instrument's configurations area, in a new folder that should be named `opcua`. If done properly, the `opcua` EPICS module should be able to pick up the user name and password, log in to the OPC server properly, and begin a connection.
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

client_private_key.pem, cert.txt

How does one acquire or generate these files? Are they something that was exported from the PLC, or something you generated?

On occasion, a client certificate needs to be trusted manually, from the PLC technician side. However, things *_should_* be set up on our PLCs currently deployed; this step is done in deployment/implementation. A security policy might be set that is not what the IOC is trying to use, if everything else seems fine but you are unable to connect. Lastly, another person might be connected to the server (perhaps testing an IOC or something), and they would need to be kicked off in order for the IOC to communicate properly. Speak with Tim Carter or a member of his team to see if this is the case.

## Where are instrument-specific configs loaded from
We load instrument specific configs from the $(INSTRUMENT)/configurations/opcua/ folder. This `opcua` folder is created at implementation time, on the `NDX` machine. It should contain a `OPCUA_01.cmd` file, which contains any `DbLoadRecords` calls, and where paths are specified to the `db` files for that `NDX`'s specific `OPCUA` IOC. If an `NDX` is missing an `opcua` folder, create one; if you cannot find it's `OPCUA_01.cmd` file, it _should_ be placed in the Experiment Controls non-public network share, in the `OPCUA` folder, in a folder specific to that `NDX`. For example, `NDXMAPS`'s `OPCUA_01.cmd` file is in `<network share>/OPCUA/MAPS_OPCUA/`.
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Suggested change
We load instrument specific configs from the $(INSTRUMENT)/configurations/opcua/ folder. This `opcua` folder is created at implementation time, on the `NDX` machine. It should contain a `OPCUA_01.cmd` file, which contains any `DbLoadRecords` calls, and where paths are specified to the `db` files for that `NDX`'s specific `OPCUA` IOC. If an `NDX` is missing an `opcua` folder, create one; if you cannot find it's `OPCUA_01.cmd` file, it _should_ be placed in the Experiment Controls non-public network share, in the `OPCUA` folder, in a folder specific to that `NDX`. For example, `NDXMAPS`'s `OPCUA_01.cmd` file is in `<network share>/OPCUA/MAPS_OPCUA/`.
We load instrument specific configs from the `$(INSTRUMENT)/configurations/opcua/` folder. This `opcua` folder is created at implementation time, on the `NDX` machine. It should contain a `OPCUA_01.cmd` file, which contains any `dbLoadRecords` calls, and where paths are specified to the `db` files for that `NDX`'s specific `OPCUA` IOC. If an `NDX` is missing an `opcua` folder, create one; if you cannot find it's `OPCUA_01.cmd` file, it _should_ be placed in the Experiment Controls non-public network share, in the `OPCUA` folder, in a folder specific to that `NDX`. For example, `NDXMAPS`'s `OPCUA_01.cmd` file is in `<network share>/OPCUA/MAPS_OPCUA/`.

Comment on lines +586 to +587
opc
opcua
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Is this the preferred stylisation - I thought it was generally OPCUA?

Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

I think it's technically "OPC UA" annoyingly

Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

OK - then probably we just need OPC and UA in the wordlist (and maybe OPCUA if we want to refer to the ioc name). But probably not opcua.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
None yet
Projects
None yet
Development

Successfully merging this pull request may close these issues.

MAPS: Provide support to read pressure values from vacuum PLC